Blink Home > Safety > Corridor Safety Requirements
Corridor Safety Requirements  
 
Summary: Learn what is permitted and prohibited in UCSD corridors to ensure building occupants have a clear pathway and safe exit in an emergency.

UCSD's Health and Safety Coordinating Council, with input from other faculty-led safety committees, developed UCSD's policy for permissible and prohibited use of equipment and storage of materials in corridors.

Click on a topic for details:

Topic Details
Definitions
  • Corridor: Any passageway connecting individual rooms and spaces to an exit door, stairwell, or other area of refuge
  • Equipment: Anything requiring electrical power to operate (copy machines, ATMs, vending machines), or which occupies a permanent footprint on the floor
  • Material: Other items such as file cabinets, desks, chairs

    Back to top

General restrictions In general, the following restrictions apply to all corridors:
  • Nothing may obstruct the required minimum width of a corridor.
  • Corridors may never be used as routine work spaces.

    Note: Corridor safety requirements also apply to the pathway out of large rooms and laboratories. Unobstructed corridors are of little value if you can't get to them.

    Back to top

Prohibited equipment and materials Any equipment, material, or activity obstructing passage through a corridor is prohibited. Specifically prohibited equipment, materials, and activities are described below.
  • Maintain a clear area around corridor eyewashes, emergency showers, and fire extinguishers. Anything that interferes with the use of corridor safety equipment is prohibited.
  • Never store or use hazardous materials in a corridor.
  • Examples of items that are not permitted include but are not limited to:
    • Refrigerators
    • Copy machines
    • ATMs
    • Storage cabinets (metal or wood)
    • Cardboard or wooden boxes
    • Pallets of chemicals
    • Trash or recycling receptacles
    • Compressed gas cylinders containing toxic or flammable gases
    • Water bottles
    • Flammable liquid storage cabinets
    • Small cryogenic liquid dewars
    • Decorative materials
  • Remove unauthorized items promptly within the required timeframe:

    • Immediately if material is hazardous (compressed gases, hazardous chemicals, etc.)
    • Within 30 days if the item is non-hazardous
Note: If you're in a healthcare setting, fire safety requirements are more restrictive. Nothing can be stored in hospital or clinic corridors. Contact Medical Center Safety and Security Services, (619) 543-7575, for more information.

Back to top

Equipment and materials that may be authorized and permitted Note: Only equipment or material authorized and tagged by Environment, Health & Safety (EH&S) may be placed in a corridor.
  • Authorized equipment and materials must meet the following criteria:
    • Conform with state fire marshal regulations
    • Be secured against movement during an earthquake
    • Be noncombustible or of limited combustibility
  • Equipment and materials that may be authorized by EH&S include the following:
    • Metal file cabinets equipped with positive-locking drawers to prevent inadvertent opening during earthquakes
    • Bulletin boards that meet the following requirements:
      • Greater than four square feet must have frames and glass fronts
      • Greater than nine square feet must have locking mechanisms in addition to frames and glass fronts
    • Pressurized containers of liquefied cryogenic gases (e.g., nitrogen) secured to the wall with a top-ring tether
    • Compressed inert gas cylinders, for storage only (e.g., argon, helium, neon, nitrogen, krypton, carbon dioxide), secured to a substantial, fixed surface with upper and lower chains
  • Contact EH&S Fire & Life Safety, (858) 822-5706 or 534-3660, to request authorization to place equipment or material in a corridor. EH&S will tag authorized items to indicate approval has been granted.

    Back to top



If you are a UCSD employee and have a question about fire safety, contact EH&S Fire & Life Safety, (858) 822-5706 or 534-3531.


Notice: In case of fire, your first responsibility is to escape unharmed and sound the alarm. Use a fire extinguisher only if you have been trained to use one and you have a clear exit path behind you.


  Print
Print
this page
  Email
Share
this page
  Add to MyBlink
Save
this link
  Get notified when this page is updated
Notify
on change
  Add a sticky note to this page
Add
a note
 
Get what you wanted?    yes   no   Comments.


Last reviewed/updated on May 14, 2008 (see more info)
Blink A-Z Index:   0-9  A B C D E F G H  I  J K L M N O P Q R S T U V W X Y Z 


Blink Home  Site Map  Help  Accessibility Tips  Privacy Statement  Content Manager  RSS Feed 


Copyright ©2008 Regents of the University of California. All rights reserved.
Official Web Page of the University of California, San Diego

Blink version 1.7 12-17/2007 Blink Usability Group