Blink Home > Safety > Handling Pyrophoric and Other Highly Reactive Materials
Handling Pyrophoric and Other Highly Reactive Materials  
 
Summary: See guidelines for working with pyrophoric and other highly reactive materials to protect yourself from injury. These material require extra precaution during use, storage, and disposal because of severe reactive properties.

Pyrophoric materials ignite spontaneously when exposed to air. Handle them with extreme care to avoid contact with air and moisture. Failure to handle these materials properly may result in serious injury or death.

See the following guidelines for handling pyrophorics and other highly-reactive materials:

Note: These guidelines are not intended to substitute for specific and rigorous training from your supervisor.

Topic How to handle it
Permission Required: Before beginning a new project, get approval from your principal investigator (PI) to work with a pyrophoric or highly reactive chemical.

Return to top

Safety training Required: The PI must provide appropriate, rigorous, and documented safety training.
  • Instruct employees about the hazards and risks of handling pyrophoric materials and how to protect themselves. Ensure that:
    • A safety protocol is written into the research procedure.
    • Material Safety Data Sheets (MSDS), the manufacturer's handling instructions, and UCSD standard operating procedures are carefully read.
  • Inform employees about possible health effects and routes of exposure (e.g., ingestion, inhalation, and skin contact). See:
  • Provide and train employees in the correct use of:
  • Make sure everyone understands what to do in case of emergency by posting emergency procedures in the lab:
  • Ensure fire extinguisher training is completed by employees who work with or near pyrophoric materials. See:
  • Keep training records that include:
    • Topics covered
    • Materials distributed
    • Date
    • Employee names
    • Employee signatures

    Return to top

Hazard assessment Evaluate the hazards before beginning work:
Emergency preparedness

fire extinguisher
Class D fire extinguisher for reactive metals

Image courtesy Lab Safety Supply

  • Know the locations and how to use the nearest:
    • Eyewash and safety shower
    • Emergency Guide
    • First aid kit
    • MSDS: Print and keep a copy with your emergency supplies.
    • Appropriate fire extinguisher: Avoid incompatible extinguishing agents:
      • Class A,B,C for pyrophoric liquids and supporting flammable solvents
      • Class D for reactive metals
        • Extinguishers containing water are not suitable for reactive metals.
        • Extinguishers containing or developing water, carbon dioxide or halons are not suitable for firefighting organolithium compounds as they react violently.
      • Contact EH&S Fire & Life Safety, (858) 822-7515, for questions regarding appropriate fire extinguishers.

  • Prepare for spills. Clean up only very small quantities and only if you have been properly trained.
Personal protective equipment

Flame resistant lab coat
Flame resistant lab coat
(Click image to enlarge)

Flame resistant lab coat detail
Flame resistant lab coat detail

Oberon Face Shield
Oberon Face Shield
Image courtesy Lab Safety Supply
Required PPE: Anyone at risk must wear:
  • Flame resistant lab coat at all times
    • Fully extend sleeves to the wrists.
    • Keep lab coat fully buttoned at all times.
  • Full-length, non-synthetic pants
  • Safety glasses or splash goggles (for higher volumes of reagents) with a face shield for work with liquids
  • Appropriate gloves
    • Never re-use disposable gloves.
  • Closed-toe shoes

Notes:

  • Never wear synthetic materials as they may ignite causing severe burns (e.g., polyester or nylon).
  • Leave all PPE in the lab when not in use.
  • EH&S may be able to provide a a Nomex® lab coat and a high impact face shield (see images at left). Contact your EH&S Research Assistance Program specialist.

Return to top

  • Control the hazards. Required:
    • Use at least 1 of the following engineering controls:
      • Fume hood: Work inside a chemical fume hood at all times.
      • Glove box: When inert or dry atmospheres are required.
      • Portable explosion shield: May also be required to control the risk of explosion.
      • Gas cabinet: Contact an EH&S Research Assistance Program specialist to ensure your cylinders meet the gas policy. See the requirements of using pyrophoric gases:
        • UCSD's compressed gas policy
        • Caution: Changing cylinders is among the most dangerous aspects of working with pyrophoric gases. Do not change out a cylinder unless you have been trained to safely do so.
    • Use less dangerous, more stable products when you can.
    • Before conducting the actual procedure, always perform a dry run to identify and resolve possible safety hazards.
    • Never work alone. Always work with a partner and inform colleagues in the area about the hazards of your project.
    • Establish a designated, restricted access area:
      • Clear the area of unrelated and possibly incompatible hazards, especially flammable liquids.
      • Keep container sizes and quantities in the work area as small as possible.
      • Transport material in secondary containers and only in small quantities.

    Return to top

    Exposure response Treat any exposure seriously, no matter how slight it may seem at the moment.
    • All exposures:
      • Be prepared to act quickly should clothing or skin catch fire.
      • Give first aid treatment, and then seek medical attention immediately as needed.
      • Call Campus Police at (858) 534-4357 (534-HELP) and request an ambulance, if transportation is necessary.
      • Call Poison Control, (800) 222-1222, if additional information is needed.
    • Ingestion: Seek medical attention immediately.
    • Skin exposure: Flush exposed skin with water for at least 15 minutes while removing any contaminated clothing.
    • Eye exposure: Flush eyes with water for at least 15 minutes. Affected individuals may need help holding their eyes open under water. Seek medical attention immediately at an emergency room.

      Return to top

    Purchasing and storage See Chemical Storage and Inventory Guidelines and follow these specifics:
    • Meet safe storage requirements for each specific material, and store:
      • Group 1 metals under mineral oil
      • Under an atmosphere of inert gas, if required
      • Organolithium compounds at temperatures 25 C or below

    • Avoid inadvertent incompatibles:
      • Heat/ flames, oxidizers, and water sources
      • CO2 and fluorocarbons react exothermically with lithium alkyls
      • Protonactive substances (e.g., alcohols, amines, mercaptanes, and acids)
      • Halogenated compounds (e.g., solvents like tetrachloromethane, chloroform), as well as compounds with multiple bonds (e.g., ketones, nitriles) and oxidizing agents react vigorously with organolithium compounds

    • Contact an EH&S Research Assistance Program specialist if you have questions about chemical and container compatibility.
    • Return to top

    Hazardous waste disposal Read these articles to help you identify and dispose of hazardous waste:


    Questions? Contact the EH&S Research Assistance Program specialist assigned to your building.


      Print
    Print
    this page
      Email
    Share
    this page
      Add to MyBlink
    Save
    this link
      Get notified when this page is updated
    Notify
    on change
      Add a sticky note to this page
    Add
    a note
     
    Get what you wanted?    yes   no   Comments.


    Last reviewed/updated on April 16, 2009 (see more info)
    Blink A-Z Index:   0-9  A B C D E F G H  I  J K L M N O P Q R S T U V W X Y Z 